Description
- Rated Voltage: 1500 Vdc
- Amperage Rating: 125-400 A
- Breaking Capacity: 50 kA
- Time Constant: 1-3 ms
- Class Type: aR
- Strong current limiting capacity
- AXE series PN in this datasheet is without microswitch
- Optional microswitch available PN: MS0003
Name of the manufacturer: ADLER Elektrotechnik Leipzig GmbH
Registered trade name/trademark: ADLER
Postal address: Haynaer Weg 16, D-04435 Schkeuditz, Germany
E-mail address: info@adlerelektro.de
- Industrial ESS and BESS protection
- Power Distribution Protection
- Designed to IEC 60269-1 / IEC 60269-6
- Certification: UL, TÜV
- Manufactured under IATF 16949 quality system
- RoHS and REACH Compliant
During transportation and storage, customer should avoid water seepage and mechanical damage.
Where the following conditions apply, fuses complying with this standard are deemed capable of operating satisfactorily withoutfurther qualification.
- Installation suggestion: Screw M10, Tightening torque 21±1 Nm
- Normal temperature: -5-40 ℃.
- The altitude of the site of installation of the fuses should not exceed 2000 m above sea level.
- The air should be clean and its relative humidity does not exceed 50 % at the maximum temperature of 40 ℃.
- Higher relative humidity’s are permitted at lower temperatures, e.g., 90 % at 20 ℃.
- Pollution grade Ⅲ
- Under these conditions, moderate condensation may occasionally occur due to variation in temperature.
- For operating conditions other that above, please contact the manufacturer.